Motorised two-way valve dedicated to fan coil units: opened and closed automatically by the thermostat signal, spring return closes it on power failure, with flexible on-site assembly and wiring.

The FV-VA7010 series on/off motorised valve consists of the VAA7010 series valve actuator and the VAV7010 series copper valve. It opens or closes the pipe run of a chilled or hot water air-conditioning system to control room temperature. The actuator is driven by a unidirectional hysteresis synchronous motor, and the valve has spring return. The valve is normally closed when idle; when operation is called for, the thermostat sends an opening signal, the motorised valve is energised and opens, chilled or hot water enters the fan coil unit and cools or heats the room. When the room reaches the thermostat set point, the thermostat cuts the power, the return spring closes the valve and shuts off the water flow into the fan coil.
The VA7010 series actuator connects to the valve body by a threaded sleeve, so the actuator can be fitted after the valve is installed — on-site assembly with flexible, convenient wiring.
Motorised control · spring return · on-site assembly · copper body
Thermostat signal control opens and closes the water flow automatically for precise temperature control.
Closes automatically on power failure by return spring — safe and reliable.
The actuator joins the body by a threaded sleeve and is fitted after installation.
Quality copper valve body: pressure-resistant, durable and well sealed.
| 1 | Read the manual carefully before installation; isolate the power and have qualified technicians carry out the work. |
| 2 | Water flow must follow the arrow marked on the valve body. |
| 3 | The body must sit above the coil drain pan so that drips fall into the pan. |
| 4 | Install the body and actuator within ±60° of vertical, leaving at least 30 mm of clearance above for servicing. |
| 5 | Two or more motorised valves must not be wired in parallel; where parallel operation is needed, isolate them with relays. |
| 6 | Fit the actuator only after the body is installed and pressure-tested. |
| 7 | With the actuator mounted on the body, do not apply force to it during commissioning. |
| 8 | Do not wrap the actuator in insulation, which would impair heat dissipation. |
| 9 | Earth the actuator reliably with a conductor of at least 1.5 mm². |
| 10 | After installation, energise and commission, watching three complete actuator cycles. |
| 11 | During water testing keep the system differential pressure within 0.15 MPa. |

A: The two valve wires go to the thermostat output (usually the valve-control output); neutral and live go to the 220 V supply. When the thermostat reaches its set point it cuts the power and the valve closes by spring return.
A: The VA-7010 series uses G3/4 or G1 female threads, the same size as standard manual ball valves, so it is a direct replacement. The actuator can be removed on its own, leaving the body in place.
A: Most leaks come from an imperfectly sealed threaded joint — check that the PTFE tape is wound properly. The body is forged brass rated 1.6 MPa and will not crack under normal conditions.
Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer
A genuine source factory with in-house R&D, so the price stays genuinely competitive.
Self-inspected and tested unit by unit, which is why buyers trust us.
Ample stock and large ready quantities, so supply capacity is strong.
Sample-based customisation and non-standard machining — call us to discuss.