DeLENG concealed horizontal fan coil units are designed for recessed ceiling installation, keeping the unit out of sight while delivering quiet cooling and heating. Copper-tube coil with hydrophilic a

DeLENG Concealed Horizontal FCU supplied direct from our Dezhou factory. Standard models and customised sizes are both available; send the project parameters and we will confirm the model and price.
Slim chassis from 200 mm — fits standard ceiling voids with a concealed installation · Copper-tube coil with hydrophilic aluminium fins · 3-speed motor as standard; EC brushless motor optional for energy saving · 2-pipe cooling-only or 4-pipe cooling + heating configuration · Condensate tray
tested at 2.0 MPa
return-air box and washable filter available
| Performance | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
|---|---|---|---|---|---|---|---|---|---|---|
| Air volume | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
| M | 260 | 390 | 510 | 640 | 770 | 1020 | 1280 | 1530 | 1790 | |
| L | 170 | 260 | 340 | 430 | 510 | 680 | 850 | 1020 | 1190 | |
| Cooling capacity | H | 2150 | 3350 | 3950 | 5050 | 5950 | 7450 | 9250 | 10950 | 12850 |
| Heating capacity | H | 1210 | 1820 | 2430 | 3030 | 3650 | 4860 | 6070 | 7290 | 8500 |
| Input power | 12Pa | 36 | 50 | 60 | 74 | 93 | 130 | 147 | 183 | 221 |
| 30Pa | 43 | 57 | 70 | 84 | 105 | 151 | 169 | 206 | 245 | |
| 50Pa | 48 | 64 | 81 | 97 | 114 | 169 | 204 | 243 | 291 | |
| Noise | 12Pa | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| 30Pa | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | |
| 50Pa | 42 | 44 | 46 | 47 | 49 | 50 | 52 | 54 | 56 | |
| Water flow | 380 | 600 | 700 | 900 | 1060 | 1330 | 1650 | 1950 | 2290 | |
| 110 | 160 | 220 | 270 | 330 | 430 | 540 | 650 | 760 | ||
| Water resistance | 24 | 14 | 19 | 22 | 31 | 13 | 24 | 29 | 42 | |
| ≤30 | ≤30 | ≤30 | ≤30 | ≤40 | ≤40 | ≤40 | ≤40 | ≤50 | ||
| Weight | 12 | 14 | 16 | 17.5 | 19 | 25 | 29.5 | 32.5 | 35.5 | |
| With return box | 15 | 18 | 20 | 22 | 24 | 31 | 36 | 40 | 44 |
| Model | A outlet length (mm) | B hanger hole length (mm) | C total length incl. drain pan (mm) | Suitable area (m²) |
| FP-34WA | 460 | 490 | 750 | 5—10 |
| FP-51WA | 580 | 610 | 850 | 10—15 |
| FP-68WA | 650 | 680 | 950 | 15—20 |
| FP-85WA | 780 | 810 | 1050 | 20—25 |
| FP-102WA | 900 | 930 | 1150 | 25—30 |
| FP-136WA | 1100 | 1130 | 1350 | 30—40 |
| FP-170WA | 1350 | 1380 | 1650 | 40—50 |
| FP-204WA | 1560 | 1590 | 1850 | 50—55 |
| FP-238WA | 1750 | 1780 | 2050 | 55—60 |

Concealed horizontal 4-pipe FCU (3+1) dimensions – A/B/C in the table below
Hotels, offices, hospitals, shopping centres, schools and residential projects — any building where a central chiller or heat pump supplies chilled or hot water to terminal units.
Q: What is the minimum order quantity?
A: One unit for standard models, and sample orders are accepted. For customised items the MOQ depends on the specification.
Q: What is the lead time?
A: Standard models are in stock and can ship the same day. Non-standard items are usually ready in 3–7 working days after order confirmation.
Q: What warranty do you provide?
A: Fan coil units carry a 3-year warranty on the unit; other products carry 18 months. Non-human damage is repaired free of charge within the warranty period.
Selection and quotation: +86 534 2555668 | WeChat 0534-2555668 | sales@deleng.com




Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer
A genuine source factory with in-house R&D, so the price stays genuinely competitive.
Self-inspected and tested unit by unit, which is why buyers trust us.
Ample stock and large ready quantities, so supply capacity is strong.
Sample-based customisation and non-standard machining — call us to discuss.