In one line: run maintenance on three levels — monthly listen to the unit, feel the airflow, check the drain; at the change of season pull the filter, wash the coil, flush the drain pan; before winter drain down, protect against frost and seal the air outlets. Six items for a fan coil unit and five for an HRV, done against a written list, and the equipment will hold for another five to eight years.
Every time the season turns, the phone starts ringing: the fan coil is not cooling, the fresh-air unit has no airflow, the rooms feel stuffy. Take the unit apart and nine times out of ten the machine is fine — the filter is blocked, the drain pan is clogged, the heat-exchange core has not been washed for a year. The equipment is not delicate; what it lacks is someone looking after it. I have spent twenty years in HVAC, and this is the year’s work for these two product families, laid out by season.
My habit is three levels. Monthly: listen, feel, look. Change of season (April and October): pull the filters, wash the coils, flush the drain pans, check the water system. Before winter (November): re-check the water circuit, apply frost protection, seal the outlets. Write all three into the maintenance book so nothing is missed whoever does the job.
Fan coil units come concealed, exposed, cassette and vertical; the structure differs but the maintenance is much the same. What we build most is the concealed horizontal fan coil unit, from FP-34 to FP-238.
A dirty filter halves the airflow, and the supply-air temperature drops with it. Wash with a neutral detergent and a soft brush; do not soak it in an alkaline solution, which oxidises and darkens the aluminium frame. Let it dry before refitting — put it back wet and it will mould over one summer and the air will smell. In offices and hospitals running all day, once a month is not excessive.

Open the access panel in the ceiling, take out the dusty return-air filter and wash it
Dust on the fins can knock 20 to 30 percent off heat transfer in a year; the machine is not broken but always short of performance. Flush along the fin direction with the pressure turned right down — aluminium fins bend at a touch and are hard to restore. Use a neutral cleaner, blow dry, straighten any bent fins with a fin comb, then check that water drains away freely.

Condensate pan, float and drain line checked together — drainage must run free
Mud and biofilm in the pan block the outlet, water overflows and soaks the ceiling. Take the pan out, clear the mud, pour in a little disinfectant, run a flexible brush through the drain line, check the fall, and do not let the discharge end sit inside a sewage well or odour will come back up. Once a month beats an emergency repair. And when the unit is installed above a ceiling, the access panel has to be big enough that the filter can actually be pulled out.
Clean the Y-strainer on the supply line, check that valves open and close fully, look for leaks at every joint. Supply/return temperature difference is a useful reading: normally about 5 °C. Too small usually means excess flow or a bypass left open; too large usually means insufficient flow or a blocked coil. Vent the high points so air does not sit in the coil.
A metallic scraping from the bearing means do not wait: change the bearing or the motor. Test every position of the three-speed switch — many faults sit in the contacts. Tighten the terminals, check insulation and earthing, and replace cracked or aged damping pads on the hangers or the low-frequency noise will travel into the slab.
In unheated workshops and stores, drain or blow the water out before shutdown; do not rely on insulation. One real freeze and the coil is scrap — the repair costs as much as a new one.
Most HRVs are total heat exchange, with either a paper core or a polymer core, and the maintenance differs. Know which one you have first.
Primary filters can be washed; medium and high-efficiency filters are best replaced. In the smog season check every month or two; in ordinary areas every three to four months. A dirty filter cuts airflow, loads the fan and raises noise — many people think the machine is ageing when it is the filter dragging it down.
A paper core must not be washed, only vacuumed; once it degrades the heat exchange, replace it. A washable core can be flushed and dried in the shade — never in direct sun, which warps it. Refit it the right way round: if the seal strips are not seated, supply and exhaust air will cross over.

Take the core out, flush it, dry it in the shade and refit it the right way round
Dust on the impeller destroys its balance, and vibration and noise follow. Isolate the power and wipe it clean. Clear the insect screen and rain hood at the outdoor intake, replace cracked flexible connectors, and set the damper to the design airflow rather than opening everything.
Reset the filter alarm, calibrate the CO2 and humidity sensors once a year, and test the summer/winter bypass mode. An alarm lamp that stays on all year means there is no alarm at all.
Take an anemometer reading at several points across the supply outlet, average it, multiply by the free area to get the airflow. Below 80 percent of the nameplate, check the filter, damper and flexible connector before suspecting the fan. Below −10 °C, add preheat or electric heating, and shut the fresh-air damper tight when the unit stops.

After maintenance, measure the supply airflow and compare it with the nameplate
A pressure washer on the coil lays the fins flat; a torn filter put back is no filter at all; washing the filter but never the pan ends in a leak; soaking a paper core writes it off; and keeping no record means next year you start from nothing.
Maintenance is not mysterious — do it on time and write it down. The same equipment lasts eight years for one owner and leaks everywhere for another within three; the difference is rarely the parts, it is whether anyone looked after it on schedule. The three models below are the ones we build most in these two families, with parameters and drawings on the product pages. If you need to size a model or an airflow, the selection and airflow tools work it out directly.