Home›Products ›Exposed Vertical FCU ›DeLENG FP Series Exposed Vertical Fan Coil Unit (Quiet, Cooling and Heating, Central AC Terminal)

DeLENG FP Series Exposed Vertical Fan Coil Unit (Quiet, Cooling and Heating, Central AC Terminal)

DELENG HVAC · Direct from our Dezhou factory  

DeLENG FP Series Exposed Vertical Fan Coil Unit
Quiet, Cooling & Heating, Central AC Terminal

DeLENG FP series exposed vertical fan coil unit, supplied direct from our Dezhou factory: reliable quality, non-standard customisation supported, widely used in commercial HVAC ventilation projects.

Cooling & heatingQuietEnergy savingStainless steelDirect from factory
DeLENG FP series exposed vertical fan coil unit

Product introduction

The FP series exposed vertical fan coil unit is a common terminal device in central air-conditioning systems. Working with a chilled and hot water loop, it provides cooling in summer and heating in winter. Units can be specified in horizontal, vertical or cassette configurations to suit the available space, and are widely used in hotels, office buildings, shopping malls, residences and commercial premises.

The DeLENG FP series exposed vertical unit is compact and flexible to install. Paired with a thermostat it delivers independent temperature control and on-demand start/stop, balancing comfort with energy savings. Non-standard customisation is supported, with fabrication and selection made to project drawings.

Service hotline:0534-2555668

Key features · Why choose the DeLENG FP series exposed vertical fan coil unit

Cooling and heating · Quiet running · Energy saving · Stainless steel

C

Cooling & heating

One unit for both seasons: cooling in summer and heating in winter from a chilled and hot water source.

Q

Quiet running

Stable, low-noise operation that suits bedrooms, offices and hotels where quietness matters.

E

Energy saving

Efficient running that reduces long-term operating costs.

S

Stainless steel

Stainless steel construction resists corrosion and cleans easily, which suits humid or kitchen areas.

Core selling points of the exposed vertical fan coil unit

Low-noise running and angled air outlet
LCD switch and thickened casing

Exposed vertical fan coil unit technical performance data

Cooling and heating · Quiet · Central AC terminal

Performance Model FP-34 FP-51 FP-68 FP-85 FP-102 FP-136 FP-170 FP-204 FP-238
Airflow m³/h High 340 510 680 850 1020 1360 1700 2040 2380
Medium 255 383 510 638 765 1020 1275 1530 1785
Low 170 255 340 425 510 680 850 1020 1190
Cooling capacity W High 1800 2700 3600 4500 5400 7200 9000 10800 12600
Medium 1440 2160 2880 3600 4320 5760 7200 8640 10080
Low 1170 1755 2340 2925 3510 4680 5850 7020 8190
Heating capacity W High 2700 4050 5400 6750 8100 10800 13500 16200 18900
Medium 2160 3240 4320 5400 6480 8640 10800 12960 15120
Low 1755 2633 3510 4388 5265 7020 8775 10530 12285
Input power W 12Pa 37 52 62 76 96 134 152 189 228
30Pa 44 59 72 87 108 156 174 212 253
50Pa 49 66 84 100 118 174 210 250 300
Noise dB(A) 12Pa 37 39 41 43 45 46 48 50 52
30Pa 40 42 44 46 47 48 50 52 54
50Pa 42 44 46 47 49 50 52 54 56
Water flow t/h 0.39 0.55 0.70 0.82 0.91 1.34 1.59 1.80 2.07
Water resistance kPa 12 16 20 23 26 28 32 38 42
Weight kg (FP-LM) 24 28 30 31 34 48 53 56 66
Water connections: DN20 female thread
Condensate drain: DN20 male thread
Power supply: Single phase 220V / 50Hz

Exposed vertical fan coil unit overall dimensions

Exposed vertical fan coil unit dimensional drawing: body length, width and height
 
Model L×W×H
mm
Input
power W
Fans Area
m²
FP-34LM 790×240×590 37 1 motor / 1 fan 5-10
FP-51LM 940×240×590 52 1 motor / 2 fans 10-15
FP-68LM 980×240×590 62 1 motor / 2 fans 15-20
FP-85LM 1100×240×590 76 1 motor / 2 fans 20-25
FP-102LM 1260×240×590 96 1 motor / 2 fans 25-30
FP-136LM 1410×240×590 134 2 motors / 3 fans 30-40
FP-170LM 1680×240×590 152 2 motors / 4 fans 40-50
FP-204LM 1880×240×590 189 2 motors / 4 fans 50-55
FP-238LM 2080×240×590 228 2 motors / 4 fans 55-60

Applications

RNV
Renovation
Surface pipework, no ceiling void
OFF
Offices
Floor-standing, ready to run
CLS
Classrooms
Vertical airflow, even and comfortable
MED
Wards and laboratories
Quiet operation, easy maintenance

FAQ

Where is the DeLENG FP series exposed vertical fan coil unit suitable for?

It suits commercial HVAC ventilation projects. Dezhou DeLENG, as the source factory, can provide a suitable selection based on the actual project requirements.

Can dimensions and specifications be customised?

Yes. The DeLENG FP series exposed vertical fan coil unit supports non-standard customisation to project drawings: dimensions, materials and surface finish can all be specified as required. Send us your project parameters and we will work through them with you.

Are you the source manufacturer?

Yes. Dezhou DeLENG Air Conditioning Co., Ltd. is a source manufacturer of HVAC equipment, producing and selling directly with no middlemen, with in-house R&D and manufacturing capability and consistent quality.

How about stock and delivery?

DeLENG is a source factory in Dezhou, Shandong, with stock on hand and fast dispatch, and customisation to samples is supported. Call 0534-2555668 for selection advice.

Related products

Why choose DeLENG?

Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer

01

Factory direct

A genuine source factory with in-house R&D, so the price stays genuinely competitive.

02

Quality assurance

Self-inspected and tested unit by unit, which is why buyers trust us.

03

Stable supply

Ample stock and large ready quantities, so supply capacity is strong.

04

Custom manufacturing

Sample-based customisation and non-standard machining — call us to discuss.

Need FP Series Exposed Vertical Fan Coil Unit?
Send your project parameters — the DeLENG technical team selects for you free of charge, factory direct supply, custom sizes available.
Contact us now+86 534 2555668
Scroll to Top