Home›Products ›Centrifugal Fans ›Smoke Extract Fan Box

Smoke Extract Fan Box

Dezhou DeLENG · factory direct supply 

Smoke Extraction Fan Box (HTFC Series)

The DeLENG HTFC centrifugal smoke extraction fan box uses an externally mounted motor and a quality double-inlet centrifugal fan. Its galvanised profile frame is light, strong and corrosion-resistant, and the unit runs for 30 min in a 280°C fire condition for smoke extraction — with an optional two-speed motor, one unit serves both daily ventilation and fire smoke extraction.

HTFC seriesExternal motor280°C smoke extractionDouble-inlet centrifugalTwo-speed motor
HTFC smoke extraction fan box

Product introduction

The DeLENG HTFC centrifugal smoke extraction fan box uses an externally mounted motor together with a quality high-efficiency double-inlet centrifugal fan, matched with a quality motor, bearings and belts. The frame is made of quality galvanised steel profiles — light, strong and corrosion-resistant. The casing panels are made of quality steel sheet and can be filled with acoustic and thermal insulation to customer requirements, so the unit runs with low noise, smoothly and reliably.

Besides normal ventilation and air exchange, this series can run for 30 min at about 280°C in a fire to extract smoke. With an optional two-speed motor it runs at low speed for daily ventilation and at high speed in a fire for smoke extraction. The product is widely used for smoke extraction and ventilation in industrial plants, high-rise buildings, hotels, civil buildings, education and healthcare premises.

Service hotline: +86 534 2555668

Key features · why choose the HTFC smoke extraction fan box

Efficient ventilation · compact and lightweight · low-noise operation · attractive and durable

E

Efficient ventilation

A quality double-inlet centrifugal fan matched with an efficient filtration system keeps air flowing freely — one unit for both normal ventilation and fire smoke extraction.

C

Compact and lightweight

A compact galvanised profile frame: small, light and easy to install and handle, saving installation space.

L

Low-noise operation

Acoustic and thermal insulation inside plus vibration damping keeps running noise low and creates a quiet environment.

A

Attractive and durable

Quality steel panels resist corrosion and last; stable operation for 30 min at 280°C means low maintenance cost and a long service life.

Product details

Quality details you can see — built for your satisfaction

Acoustic lining

Acoustic lining

Acoustic panels and rubber damping pads are fitted inside, so running noise and vibration are low for a quiet environment.

High-efficiency filtration

High-efficiency filtration

An efficient filtration system removes dust and impurities from the air, keeping the supply air clean and the airflow free.

Copper-core motor

Copper-core motor

The motor is matched to the impeller and casing so its temperature stays within the national standard, giving stable long-term running.

Galvanised profile frame

Galvanised profile frame

Quality galvanised steel profiles make the frame light, strong, corrosion-resistant and rigid for reliable unit operation.

HTFC-I series · smoke extraction fan box performance parameters

Single-speed smoke extraction duty · complete factory performance data

No. Model Airflow(m³/h) Total pressure(Pa) Power(kW) NoisedB(A) Reference weight(kg)
1 HTFC-I-10 1400-3000 240-290 0.55 67 125
2300-3500 360-270 0.75 67 125
2200-4500 290-380 1.1 71 140
2700-5100 330-520 1.5 71 145
3600-5500 330-520 2.2 71 155
4400-6300 520-670 3 75 155
2 HTFC-I-12 2200-3100 340-270 0.75 65 150
2600-4200 450-300 1.1 68 155
3100-6100 490-300 1.5 71 160
3400-6600 650-420 2.2 74 175
4800-7800 670-400 3 74 175
6400-8400 690-510 4 76 180
2200-3000 290-340 0.75 66 155
2600-4100 480-350 1.1 69 165
2800-5700 560-380 1.5 73 165
3100-5600 290-370 1.5 72 180
4100-7300 620-420 2.2 77 180
6300-6900 290-430 2.2 76 215
5200-8600 520-620 3 81 180
7200-9500 700-560 4 83 185
8600-11100 670-710 5.5 86 215
3 HTFC-I-15 2700-5900 310-190 1.1 65 215
3000-5700 520-380 1.5 70 215
4100-7300 260-430 1.5 69 230
4000-6800 630-430 2.2 72 230
6100-8000 450-290 2.2 71 235
4400-9900 710-480 3 76 230
7200-9900 500-380 3 74 265
5400-11000 1000-480 4 77 235
9200-11100 500-480 4 76 265
7300-12200 990-610 5.5 79 265
10000-14000 1060-610 7.5 80 270
4300-5600 380-340 1.5 70 230
4700-8300 570-380 2.2 72 245
4300-10400 460-290 2.2 72 250
5200-10400 700-420 3 74 245
7400-11900 530-300 3 75 280
6400-12200 890-450 4 76 250
9000-13100 560-400 4 76 280
6500-14200 960-440 5.5 77 275
11300-14600 560-480 5.5 78 280
8600-16500 1090-680 7.5 82 280
13300-18900 1240-670 11 82 335
14900-20800 1180-1140 15 87 340
4 HTFC-I-18 5100-8000 470-370 2.2 72 280
4900-11100 410-290 2.2 72 285
6300-11600 610-420 3 75 280
6100-12400 550-310 3 74 315
7000-13200 760-440 4 76 285
8900-14300 590-380 4 76 320
7700-17200 950-460 5.5 79 315
11000-16900 620-460 5.5 79 320
8600-19100 1190-620 7.5 82 320
15400-18600 640-360 7.5 80 370
10300-21200 1240-710 11 83 370
13900-23100 1360-890 15 86 375
18800-23800 1350-1240 18.5 88 420
5 HTFC-I-20 6900-14000 420-350 3 74 330
7700-14500 460-290 3 73 365
8000-15100 610-380 4 75 335
9900-17000 520-390 4 77 370
9500-19200 760-440 5.5 78 365
12900-23100 560-350 5.5 78 370
10500-20600 1050-440 7.5 79 370
16200-23800 590-410 7.5 79 420
11700-25000 1150-720 11 84 420
16200-29400 1230-710 15 85 425
22700-30900 1270-900 18.5 87 465
24800-29800 1340-1190 22 89 470
6 HTFC-I-22 7900-14300 420-260 3 74 380
10600-19900 460-290 4 78 395
9900-18700 660-460 5.5 80 420
13600-23100 500-300 5.5 80 425
12200-24200 850-480 7.5 83 425
18300-26900 550-410 7.5 83 480
13600-29800 1050-570 11 86 480
23400-29000 540-510 11 85 485
26300-33200 1120-690 15 88 485
23100-35800 1150-800 18.5 90 525
28200-35100 1200-950 22 91 530
31800-41500 1200-1030 30 93 580
7 HTFC-I-25 21800-24800 360-290 5.5 76 470
13600-30500 630-310 7.5 79 475
14500-28500 830-630 11 82 530
21300-33700 670-410 11 81 535
19800-36000 1100-670 15 85 535
30600-39000 670-570 15 84 580
21300-41300 1250-720 18.5 87 575
24300-43900 1320-840 22 88 580
31300-46500 1270-910 30 89 635
40300-48500 1430-1170 37 91 720
46100-50800 1330-1460 45 92 725
8 HTFC-I-28 17400-34700 570-370 7.5 80 625
20900-24900 790-760 11 84 625
19500-40900 710-390 11 82 630
21900-30000 900-770 15 84 630
26100-46300 790-480 15 84 670
24700-44600 1110-760 18.5 87 665
36000-49500 820-670 18.5 87 725
26200-46000 1240-860 22 88 670
45400-50900 710-670 22 87 725
28200-56100 1360-920 30 90 725
37600-61000 1450-940 37 91 815
9 HTFC-I-30 30000-35400 580-510 11 81 760
30100-48400 800-540 15 84 765
31700-59400 880-480 18.5 85 805
34700-59400 980-670 22 86 810
37600-46200 1170-1140 30 88 860
35500-65000 1140-730 30 89 955
41500-50500 1330-1190 37 89 950
43000-66500 1180-900 37 91 1035
60200-74700 1160-1030 45 92 955
62600-83300 1320-1140 55 94 1035
10 HTFC-I-34 31000-60200 650-420 15 83 870
36000-44100 740-670 18.5 85 915
34900-65200 730-470 18.5 85 970
39600-52600 840-750 22 87 920
38700-57400 820-670 22 86 970
41500-77200 1050-590 30 88 970
71100-78300 850-860 37 90 1060
49900-83600 1140-730 37 90 1140
75100-90700 990-860 45 92 1070
59400-92400 1140-830 45 92 1380
67500-96800 1260-920 55 93 1140
90000-99000 1240-1140 75 94 1370
11 HTFC-I-37 39500-68100 630-440 18.5 94 1010
45000-74900 690-510 22 94 1020
48300-79900 920-580 30 97 1060
53600-62100 940-930 37 99 1160
52300-92300 1030-720 37 99 1240
56500-84200 1180-890 45 100 1170
55100-99000 1160-740 45 100 1470
76700-99100 1120-1030 55 101 1240
63000-99000 1300-910 55 101 1480
78900-111000 1300-1060 75 103 1470
99000-126000 1240-1380 90 106 1480
12 HTFC-I-40 82944-105800 610-630 30 96 1300
105800-124000 630-610 37 98 1450
124000-143000 650-620 45 99 1550
119000-139000 850-830 55 100 1800
139000-170800 950-900 75 102 2080
150000-171000 1080-1000 90 105 2150

HTFC-II series · two-speed smoke extraction / ventilation fan box performance parameters

High / low speed duty · ventilation in normal times, smoke extraction in a fire

No. Model Airflow(m³/h) Total pressure(Pa) Power (high/low)(kW) NoisedB(A) Reference weight(kg)
1 HTFC-II-10 4900 820 2.2/1.5 64 145
5400 800 64 145
6100 800 64 145
3200 370 56 145
3600 360 56 145
4100 360 56 145
2 HTFC-II-12 5300 910 4/3 64 205
9000 970 64 205
12600 730 65 205
3500 400 60 205
6000 420 60 205
8300 320 61 205
3 HTFC-II-15 6000 820 5.5/4 66 300
10800 740 66 300
17900 600 67 300
4000 360 62 300
7200 330 62 300
11900 260 63 300
4 HTFC-II-18 7600 970 8/6.5 69 395
12800 900 69 395
22200 680 70 395
5000 420 63 395
8500 400 63 395
14800 300 64 395
5 HTFC-II-20 14000 970 11/9 70 505
21700 910 70 505
31300 600 71 505
9400 420 64 505
14400 400 64 505
20800 260 65 505
6 HTFC-II-22 26200 890 14/11 73 620
31800 740 73 620
37400 530 74 620
17400 400 69 620
21200 220 69 620
25000 240 70 620
7 HTFC-II-25 31200 960 17/8 72 735
37000 840 72 735
46200 620 73 735
20600 420 69 735
24500 360 69 735
30600 280 70 735
8 HTFC-II-28 32900 850 20/15 73 880
44200 820 73 880
56500 680 74 880
24700 480 70 880
33100 470 70 880
42400 380 71 880
9 HTFC-II-30 48000 960 30/15 73 1000
63400 940 73 1000
78000 660 74 1000
36200 540 70 1000
47800 530 70 1000
58800 380 71 1000
10 HTFC-II-34 55200 1070 35/20 74 1050
70600 1010 74 1050
83400 840 75 1050
41400 600 71 1050
52900 560 71 1050
62500 480 72 1050
11 HTFC-II-37 62500 1030 37/18 75 1120
70700 1020 75 1120
84100 900 76 1120
46900 580 72 1120
53000 560 72 1120
63200 500 73 1120
12 HTFC-II-40 115000 1070 45/22 77 1200
124000 990 77 1200
132500 930 79 1200
76800 780 75 1200
82500 730 75 1200
98000 620 76 1200

Performance data are factory test values; selection is confirmed against the project duty.

HTFC series smoke extraction fan box outline dimensions (motor side-mounted)

A: horizontal inlet, 180° outlet · B: horizontal inlet, 90° outlet · unit outline dimension table (unit: mm)

Horizontal inlet, 180° outlet
Horizontal inlet, 90° outlet

Unit outline dimension table (unit: mm)

No. Model L L₁ W H A B E F K
1△ HTFC-I-10 1130~1280 600 600 550 460 410 460 410 63
2△ HTFC-I-12 1260~1430 700 700 650 560 510 560 510 63
3 HTFC-I-15 1540~1740 900 900 850 600 600 760 710 63
4 HTFC-I-18 1680~1960 1000 1000 950 700 700 860 810 100
5 HTFC-I-20 1830~2060 1100 1100 1050 750 750 960 910 100
6 HTFC-I-22 1980~2210 1250 1250 1150 850 850 1110 1010 100
7 HTFC-I-25 2140~2330 1350 1350 1300 900 900 1210 1160 100
8 HTFC-I-28 2370~2590 1550 1550 1450 1050 1050 1410 1310 100
9 HTFC-I-30 2660~2860 1700 1700 1600 1200 1200 1560 1460 100
10 HTFC-I-34 2810~3060 1850 1850 1750 1300 1300 1710 1610 100
11 HTFC-I-37 2920~3320 1950 1950 1900 1400 1400 1810 1760 100
14 HTFC-I-40 3170~3570 2200 2200 2150 1600 1600 2060 2010 100

HTFC series smoke extraction fan box outline dimensions (motor rear-mounted)

A: side inlet, 180° outlet · B: horizontal inlet, 90° outlet · unit outline dimension table (unit: mm)

Side inlet, 180° outlet
Horizontal inlet, 90° outlet

Unit outline dimension table (unit: mm)

No. Model L L₁ W H A B E F K
1 HTFC-I-10 1170~1280 600 600 550 460 460 460 410 63
2 HTFC-I-12 1270~1380 700 700 650 560 560 560 510 63
3 HTFC-I-15 1550~1630 900 900 850 600 600 760 710 63
4 HTFC-I-18 1680~1820 1000 1000 950 700 700 860 810 100
5 HTFC-I-20 1780~1920 1100 1100 1050 750 750 960 910 100
6 HTFC-I-22 1930~2070 1250 1250 1150 850 850 1110 1010 100
7 HTFC-I-25 2080~2210 1350 1350 1300 900 900 1210 1160 100
8 HTFC-I-28 2280~2460 1550 1550 1450 1050 1050 1410 1310 100
9 HTFC-I-30 2460~2670 1700 1700 1600 1200 1200 1560 1460 100
10 HTFC-I-34 2670~2820 1850 1850 1750 1300 1300 1710 1610 100
11 HTFC-I-37 2770~3010 1950 1950 1900 1400 1400 1810 1760 100
12 HTFC-I-40 2970~3200 2200 2200 2150 1600 1600 2060 2010 100

HTFC series smoke extraction fan box outline dimensions (motor top-mounted)

Motor mounted on top of the casing · unit outline dimension table (unit: mm)

Motor top-mounted arrangement

Unit outline dimension table (unit: mm)

No. Model L W H A B E F K
1 HTFC-I-10 600 600 550 460 460 460 410 63
2 HTFC-I-12 700 700 650 560 560 560 510 63
3 HTFC-I-15 900 900 850 600 600 760 710 63
4 HTFC-I-18 1000 1000 950 700 700 860 810 100
5 HTFC-I-20 1100 1100 1050 750 750 960 910 100
6 HTFC-I-22 1250 1250 1150 850 850 1110 1010 100
7 HTFC-I-25 1350 1350 1300 900 900 1210 1160 100
8 HTFC-I-28 1550 1550 1450 1050 1050 1410 1310 100
9 HTFC-I-30 1700 1700 1600 1200 1200 1560 1460 100

Product photos

Custom manufacturing available — contact us for your requirements

Front view

Front viewFRONT SIDE
Impeller side

Impeller sideIMPELLER SIDE
Body and drive

Body and driveDRIVE SIDE
Motor side

Motor sideMOTOR SIDE
Unit on base frame

Unit on base frameBASE FRAME

Applications

HTFC smoke extraction fan box · fire smoke extraction and daily ventilation

I

Industrial plants

Smoke extraction and ventilation for industrial plants and workshops

H

High-rise buildings

Smoke extraction for high-rise buildings and large civil premises

H

Hotels and public buildings

Ventilation and smoke extraction for hotels and public buildings

E

Education and healthcare

Smoke extraction and air exchange for schools, hospitals and clinics

FAQ

Q: What is the HTFC smoke extraction fan box used for?

A: It serves both daily ventilation and fire smoke extraction: in a fire it runs for 30 min at about 280°C. With a two-speed motor the low speed covers normal ventilation and the high speed covers smoke extraction.

Q: What is the difference between the HTFC-I and HTFC-II series?

A: HTFC-I is the single-speed smoke extraction fan box; HTFC-II is the two-speed smoke extraction and ventilation fan box, with power ratings given for both the high and the low speed.

Q: Can the unit be customised, and how is it supplied?

A: Frame, panel insulation, motor position (side, rear or top) and unit size can all be made to project drawings. Call +86 534 2555668 for selection advice, stock and delivery.

Related products

Why choose DeLENG?

Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer

01

Factory direct

A genuine source factory with in-house R&D, so the price stays genuinely competitive.

02

Quality assurance

Self-inspected and tested unit by unit, which is why buyers trust us.

03

Stable supply

Ample stock and large ready quantities, so supply capacity is strong.

04

Custom manufacturing

Sample-based customisation and non-standard machining — call us to discuss.

Need a smoke Extract Fan Box?
Send your project parameters — the DeLENG technical team selects for you free of charge, factory direct supply, custom sizes available.
Contact us now+86 534 2555668
Scroll to Top