The last few days the calls have all been about the same thing: now that it is cold, do we leave the fresh-air system running?
One customer switched theirs off as soon as winter came, and now the bathroom mirror is wet every day and damp is creeping up the bedroom wall. Another, on a project, stopped the unit last winter because the rooms felt cold; when he started it in spring the heat exchange core leaked air — opened up, the core had split from freezing.
I have been in HVAC in Dezhou for twenty years and have seen plenty of these. Here are the five questions people ask most, so you can decide what to do with the unit in your own building.
Yes — and preferably without stopping. Fresh air is not just about ventilation: it carries indoor humidity, cooking fumes and bathroom odours out. Once the windows are shut for winter, that moisture has nowhere to go, which is how windows start running with water, walls turn damp and timber floors lift. On office projects where the fresh-air unit was stopped for the winter, the following year brought a steady stream of call-outs for mouldy ceilings and dripping outlets.
It can freeze — but usually because it was stopped, not because it was running. A total heat exchange core holds condensate; stop the unit below zero and the water stays inside and freezes, and the expansion splits the core. Start it again and the airflow finishes the job; paper cores and rotary wheels suffer most. For northern projects I always do the same three things: continuous running through the winter, a snow hood on the intake, insulation on the outdoor ducting — and where the outdoor temperature sits below −15 °C for long periods, a preheat coil or electric preheater.
Work per person: 30 m³/h each is the baseline. In winter you can run 20 to 30 percent below the design figure, but do not go below 20 m³/h per person — under that, CO2 climbs and people feel stuffy and sleepy. A domestic unit rated 100 m³/h on medium speed is enough for a three-bedroom flat in winter. For offices, count people, not floor area; sizing by area is usually either too big or too small.
A total heat exchanger recovers most of the heat from the exhaust air, typically 60 to 70 percent efficiency, so what actually leaves the building is modest. If running it clearly costs you heat, check three things first: is the bypass damper open, is the filter blocked, is the supply outlet blowing straight at people. The bypass is for summer; in winter it must be closed, or the heat recovery does nothing.
Three jobs: clean the filters every two weeks (winter dust is no lighter than summer dust); test the low-temperature alarm and frost protection rather than finding out they were never wired when the unit freezes; and if the outdoor unit has a condensate line, confirm ice has not blocked it, because blocked water backs up into the unit. And after a long trip away, do not go straight to maximum — run on low for half an hour and let the core settle.
Winter fresh air is not about saving electricity — it is about not stopping the unit. Continuous low-speed running is far safer than switching on and off.
If your unit is already the one that gets switched off every winter, start with HRV shut down every winter? Three settings are usually the cause. On how much air volume to specify, and the drawbacks of oversizing, see Is a bigger fresh-air volume always better? And for what a neglected filter does, What happens when an HRV filter is never cleaned.
Total heat exchange fresh-air ventilator — dual-flow total heat recovery, recovering 60 to 75 percent of the exhaust heat in winter.
HRV range — selected by air volume and installation type, commercial and domestic, 150 to 10,000 m³/h.
I am Wei Xulin of Dezhou DeLENG Air Conditioning; twenty years on fan coil units, cooling coils, fresh air and air handling units. What is above comes from workshops and sites, not from textbooks. If you have a specific selection question, send the air volume, area and clear height and I will work it out for the project.