Home›Products ›Mixed Flow Fans ›SJG Diagonal Flow Fan (Mixed-flow)

SJG Diagonal Flow Fan (Mixed-flow)

Dezhou DeLENG · factory direct supply  

SJG Diagonal Flow Fan

DeLENG SJG diagonal flow fans use a drum-shaped casing that combines the high pressure of centrifugal fans with the high airflow of axial fans — low noise, low power consumption, compact build; 200~25,000 m³/h, 50~1,200 Pa.

Diagonal flowDrum casing recovers static pressureLow noise, energy savingExplosion-proof / VFD readyCompact structure  
SJG diagonal flow fan by DeLENG, drum-type casing

Product introduction

DeLENG SJG series diagonal flow fans redirect the airflow through a drum-shaped casing to create mixed flow, combining the higher pressure coefficient of centrifugal fans with the larger flow coefficient of axial fans: low noise, low power consumption and a compact structure.

Impeller sizes run from 200 to 800 mm across more than a dozen models, with series air volume from 200~25,000 m³/h and total pressure from 50~1,200 Pa. To match different duty points, VFD motors and controllers can be supplied for speed control; we recommend locking the adjustment frequency between 25 Hz and 50 Hz.

For hazardous areas the fan can be built explosion-proof to ExdIIBT4Gb. To suit different site noise limits, fans can be supplied with silencers of different lengths, or as a fully clad (casing-silenced) version.

Working conditions: ambient temperature -20 to +40 °C; humidity below 90%; medium: air (dust content up to 100 mg/m³); power supply: three-phase 380 V / 50 Hz.

Standard supply: impeller, motor, casing (outer cylinder, guide vanes, inner cylinder, motor bracket) and base feet. Options and accessories: vibration isolators, control box, protective screen, matching flange.

Manufacturing: the impeller is steel; the hub is hydraulically drawn, the blades are stamped and then hydraulically formed and welded to the hub; the impeller is statically and dynamically balanced to G5.6 or better. The outer cylinder flange is integrally flanged and spun.

Service hotline: +86 534 2555668

Key features · Why choose the SJG diagonal flow fan

High efficiency · Low noise · Compact structure · Drum-type casing

H

High efficiency & energy saving

Mixed-flow design combines the high total pressure of centrifugal fans with the high airflow of axial fans; VFD speed control saves power in long-term operation.

L

Low-noise running

Optimised impeller and drum casing, with an optional silencer or clad casing, keep running noise low.

C

Compact structure

Smaller than a centrifugal fan of the same duty, it saves installation space — ideal where duct space is tight.

D

Drum-type casing design

The drum casing redirects the airflow and recovers static pressure, raising pressure and efficiency for steady, efficient running.

Product details

Quality details you can see, built for your satisfaction

SJG diagonal flow fan: side view of the drum casing
Side view
Drum-type casing: grey shell with a red outlet, compact and neat.
SJG diagonal flow fan: red impeller seen from the inlet
Inlet view
Red impeller with an all-copper motor and a side terminal box for easy maintenance.
SJG diagonal flow fan: heavy-duty curved impeller
Heavy-duty impeller
Curved blades, firmly welded: high airflow and high efficiency.
SJG diagonal flow fan: red folded base feet
Base feet
Red folded base feet resist vibration for steady, reliable installation.

SJG Diagonal Flow Fan Performance Data

Model Speed
(r/min)
Air volume
(m³/h)
Total pressure
(Pa)
Motor model Power
(kW)
Noise
dB(A)
Weight
(kg)
2F 1450 200 110 Y561-4 0.06 58 16
400 91
500 70
600 54
2.5F 1450 300 180 Y632-4 0.18 60 24
450 165
600 150
1000 110
3F 1450 500 260 Y712-4 0.37 61 27
750 240
1500 170
2000 130
3.5S 960 800 140 Y712-6 0.25 59 42
1500 100
2000 80
2500 50
3.5F 1450 1000 320 Y801-4 0.55 61 45
2000 250
3000 190
4000 110
4S 960 1000 190 Y801-6 0.37 60 61
2000 150
3000 100
4000 51
4F 1450 1500 420 Y802-4 0.75 62 67
2500 390
4000 280
5000 220
5S 960 1500 360 Y90S-6 0.75 63 90
2500 290
4000 240
6000 150
5F 1450 2000 710 Y100L1-4 2.2 69 110
4000 580
7000 480
10000 345
6S 960 3000 480 Y100L-6 1.5 65 150
6000 360
8000 297
11000 240
6F 1450 4000 1200 Y132S-4 5.5 75 165
8000 870
12000 690
18000 380
7S 960 4000 600 Y132S-6 3 72 215
8000 500
15000 350
18000 260
8E 720 6000 700 Y160M1-8 4 68 372
10000 585
15000 510
25000 210
8S1 960 6000 780 Y132M2-6 5.5 71 320
10000 700
15000 600
25000 400

Note: the data above are for standard duty conditions; VFD speed control or non-standard customisation can be provided to suit project requirements.

SJG Diagonal Flow Fan Outline Dimensions

SJG Diagonal Flow Fan Outline Dimensions

SJG Diagonal Flow Fan Dimension Table (mm)

Model D1 D2 D3 D4 L M1 M2 N1 N2 n-φa φb H
2 φ210 φ245 φ280 φ357 265 217 181 220 170 4-φ8.5 φ8.5 190
2.5 φ260 φ290 φ330 φ430 345 297 261 220 170 4-φ8.5 φ8.5 230
3 φ310 φ340 φ380 φ503 420 360 316 300 240 8-φ8.5 φ11 270
3.5 φ360 φ390 φ430 φ575 492 430 386 300 240 8-φ11 φ11 310
4 φ410 φ450 φ485 φ652 570 508 464 300 240 8-φ11 φ11 340
4.5 φ460 φ500 φ540 φ726 648 568 542 400 320 12-φ11 φ13 380
5 φ510 φ550 φ590 φ800 720 658 614 400 320 12-φ11 φ13 420
6 φ610 φ650 φ694 φ950 875 811 749 500 400 12-φ11 φ16 500
7 φ710 φ750 φ800 φ1100 1020 789 727 600 480 16-φ11 φ16 570
8 φ810 φ850 φ900 φ1242 1170 1084 1022 600 480 16-φ13 φ16 640

Product photos

Custom sizes available — contact us for details

SJG diagonal flow fan, inlet side
SJG diagonal flow fan, side construction
SJG diagonal flow fan, rear construction
SJG diagonal flow fan, outlet side view

Applications · Mixed-flow ventilation systems

I

Industrial & mining

Workshop ventilation

H

Hotels & restaurants

Commercial space ventilation

C

Civil buildings

Office building ventilation

M

Museums & gymnasiums

Public venue ventilation

FAQ

Q: How does the SJG diagonal flow fan differ from an axial fan?

A: The airflow of a mixed-flow fan sits between centrifugal and axial: it keeps the higher pressure of a centrifugal fan and the high airflow of an axial fan. Total pressure is higher than an axial fan and the unit is more compact than a centrifugal fan — well suited to duct booster supply.

Q: Can the fan be supplied as an explosion-proof unit?

A: Yes — rated ExdIIBT4Gb for flammable gas atmospheres. Please state the explosion-proof requirement on the order.

Q: Can airflow and pressure be customised?

A: Impeller sizes from 200 to 800 mm cover more than a dozen models; VFD motors (25~50 Hz) are available, and non-standard units can be built to your system resistance and airflow.

Q: Is the fan noisy?

A: Silencers of different lengths, or a clad (casing-silenced) version, can be supplied to suit site noise limits and effectively reduce running noise.

Related products

Why choose DeLENG?

Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer

01

Factory direct

A genuine source factory with in-house R&D, so the price stays genuinely competitive.

02

Quality assurance

Self-inspected and tested unit by unit, which is why buyers trust us.

03

Stable supply

Ample stock and large ready quantities, so supply capacity is strong.

04

Custom manufacturing

Sample-based customisation and non-standard machining — call us to discuss.

Need SJG Diagonal Flow Fan?
Send your project parameters — the DeLENG technical team selects for you free of charge, factory direct supply, custom sizes available.
Contact us now+86 534 2555668
Scroll to Top