On the DeLENG square wall-mounted axial fan the motor and impeller sit inside a round barrel, while the whole unit is square so it fits a wall opening neatly. CAD/CAM design gives high airflow at low noise, a self-closing louver at the outlet keeps out dust and rain, and the fan can either blow air in or exhaust air out.

The DeLENG square wall-mounted axial fan is built from cold-rolled steel sheet: the motor and impeller are integrated in a round barrel, and the outer casing is square, so it is easier to install in a wall and saves more space than a conventional round axial fan. A low-noise fan motor drives the impeller directly, giving steady running, high efficiency, high airflow, low noise, low power consumption and a long service life.
A square opening left in the wall is all the site work needed. The outlet is fitted with a self-closing louver that opens and closes automatically, keeping rain and natural wind from flowing back into the room and keeping dust out. The fan can both supply and exhaust air, which makes it a natural choice for wall-mounted ventilation in modern factories, industrial and mining plants, commercial and residential buildings, sports halls, livestock houses and entertainment venues.
Service hotline: +86 534 2555668
A low-noise motor drives the impeller directly — high transmission efficiency, simple structure, stable in long-term running.
Leave a square opening in the wall and set the whole unit into it: no indoor floor space is taken up and installation or removal is quick.
The outlet louver closes by itself when the fan stops, preventing rain from flowing back and keeping foreign objects out.
Supply and exhaust duty can be switched as required — high airflow, steady running and low energy use.
Quality details you can see — built for your satisfaction
CTBZ series wall-mounted fan performance data · the last letter of the model (F/E/S/T) marks the speed variant
| Model | Airflow(m³/h) | Static pressure(Pa) | Speed(r/min) | Motor power(kw) | NoisedB(A) |
|---|---|---|---|---|---|
| 2.2F | 400 | 29.0 | 1450 | 0.025 | 54 |
| 2.5F | 1000 | 52.0 | 1450 | 0.060 | 60 |
| 2.5T | 2000 | 216 | 2900 | 0.370 | 72 |
| 2.8F | 1230 | 45.0 | 1450 | 0.040 | 60 |
| 3.0F | 1650 | 58.0 | 1450 | 0.060 | 60 |
| 3.2T | 3000 | 205 | 2900 | 0.550 | 75 |
| 3.6F | 2480 | 73.0 | 1450 | 0.090 | 63 |
| 4.0S | 3370 | 76.0 | 1450 | 0.120 | 63 |
| 4.0F | 5000 | 98 | 960 | 0.25 | 63 |
| 5000 | 165 | 1450 | 0.37 | 67 | |
| 4.5F | 5870 | 121 | 1450 | 0.25 | 65 |
| 6360 | 139 | 1450 | 0.37 | 66 | |
| 5.0E | 6000 | 79 | 720 | 0.75 | 63 |
| 5.0S | 7000 | 126 | 960 | 0.55 | 68 |
| 5.0F | 8100 | 162 | 1450 | 1.1 | 73 |
| 5.6S | 7410 | 82 | 1450 | 0.37 | 69 |
| 6.3E | 9500 | 89 | 720 | 2.20 | 67 |
| 6.3S | 12000 | 190 | 960 | 1.1 | 75 |
| 6.3F | 15000 | 290 | 1450 | 2.2 | 79 |
| 7.0E | 14500 | 140 | 720 | 1.1 | 72 |
| 7.0S | 20000 | 210 | 960 | 2.2 | 78 |
| 7.0F | 25000 | 320 | 1450 | 3.0 | 80 |
| 8.0E | 22000 | 160 | 720 | 1.5 | 76 |
| 8.0S | 25000 | 197 | 960 | 2.2 | 80 |
| 8.0F | 28000 | 290 | 1450 | 4.0 | 82 |
| 10.E | 38000 | 220 | 720 | 3.0 | 81 |
| 10.5S | 48500 | 120 | 960 | 5.0 | 85 |
CTBZ series wall-mounted fan outline and wall opening dimensions (mm)
| Model | Fan outline A×A | Fan length C | Fan outline B×B | Recommended wall opening |
|---|---|---|---|---|
| 2.2 | 280×280 | 250 | 320×320 | 300×300 |
| 2.5 | 310×310 | 250 | 350×350 | 330×330 |
| 2.8 | 340×340 | 250 | 380×380 | 360×360 |
| 3.2 | 370×370 | 250 | 400×400 | 390×390 |
| 3.6 | 420×420 | 250 | 450×450 | 440×440 |
| 4.0 | 470×470 | 310 | 500×500 | 490×490 |
| 4.5 | 520×520 | 310 | 550×550 | 540×540 |
| 5.0 | 570×570 | 310 | 620×620 | 590×590 |
| 5.6 | 620×620 | 310 | 670×670 | 640×640 |
| 6.0 | 700×700 | 480 | 730×730 | 720×720 |
| 7.0 | 770×770 | 480 | 810×810 | 790×790 |
Note: models 8 to 11.2 are large units and must be made to order for the project.
Strong manufacturing base · custom sizes on request
Spot cooling and ventilation for workshops, heat dissipation for equipment — exhausted straight through the wall.
Air change for offices, homes and basements; low noise so work is not disturbed.
Auxiliary exhaust and air circulation for large spaces; several units can be installed side by side.
Air change, cooling and ammonia removal for livestock and poultry sheds; the louver keeps rain and backflow out.
A: The square wall-mounted unit has a square outer casing with the motor and impeller integrated in a round barrel, and it is designed for wall installation. A square opening in the wall is enough; it sits flatter against the wall and saves more space than a round fan, and the outlet has a self-closing louver that keeps rain and backflow out.
A: Leave a square opening that matches the fan outline, set the fan into it and fix it with bolts. Send us the model and the DeLENG technical team will confirm the required opening size for you.
A: The louver opens automatically while the fan runs and closes under its own weight when the fan stops. That prevents rain and natural wind from flowing back into the room and keeps dust out, which is why it suits external wall installation.
A: The whole unit is made of cold-rolled steel sheet, robust and durable, and the surface can be painted for rust protection. Non-standard sizes, materials and surface finishes can be built to project requirements — send the project data and DeLENG will help with selection.
A: A low-noise fan motor drives the impeller directly, so running is steady and quiet. The fan both supplies and exhausts air and suits wall-mounted ventilation in industrial and mining plants, commercial and residential buildings, sports halls, livestock houses and entertainment venues.
Dezhou DeLENG Air Conditioning Co., Ltd. · HVAC equipment manufacturer
A genuine source factory with in-house R&D, so the price stays genuinely competitive.
Self-inspected and tested unit by unit, which is why buyers trust us.
Ample stock and large ready quantities, so supply capacity is strong.
Sample-based customisation and non-standard machining — call us to discuss.